Breimer-Roth BDVA 80000

Average usage is 239 watts


TypeMeasured
Normal/Idle239.00 watts
Standby239.00 watts
Max1432.00 watts
DescriptionMeasured using Sagemcom T210-D. Transformer Dyn5, core M165-35A (142kg) only connected with its secondary side to the power grid at 400VAC, primary side 480VAC open. Temperature ambient: 3 ÂșC. Labeled P0: 184 watts.
Submit info2020-01-01 21:24:28